British BS88 - 690V: 6-710A BS88 style stud-mount fuses
EET series, BS 88 standard double tube fast fuse
Catalogue symbol:
-
(amps)CT (6 to 20 A)
-
(amps)ET (25 to 80 A)
-
(amps)FE (35 to 100 A)
-
(amps)EET (90 to 160 A)
-
(amps)FEE (100 to 200 A)
-
(amps)FM (180 to 350 A)
-
(amps)FMM (400 to 700 A)
-
(amps)MT (160 to 355 A)
-
(amps)MMT (180 to 710 A)
Description:BS88 style high speed fuse links.
Technical data
-
Rated voltage
Catalogue numbers |
IEC |
UL |
||
V a.c. |
V d.c. |
V a.c. |
V d.c. |
|
CT |
690 |
500 |
700 |
500 |
ET |
690 |
500 |
700 |
500 |
FE |
690 |
500 |
700 |
500 |
EET |
690 |
500 |
700 |
500 |
FEE |
690 |
500 |
700 |
500 |
FM |
690 |
450 |
700 |
500 |
FMM |
690 |
450 |
700 |
- |
MT |
690 |
350 |
700 |
- |
MMT |
690 |
350 |
700 |
- |
-
Rated current
-
6 - 710 A
-
Operating class: aR
-
Breaking capacity
Catalogue numbers |
IEC |
UL |
||
RMS Sym |
DC at rated voltage |
RMS Sym |
DC at rated voltage |
|
CT |
90 kA |
40 kA at 500V d.c. |
200 kA |
50 kA at 500V d.c |
ET |
200 kA |
50 kA at 500V d.c. |
200 kA |
50 kA at 500V d.c |
FE |
||||
EET |
||||
FEE |
||||
FM |
200 kA |
40 kA at 450V d.c. |
200 kA |
50 kA at 500V d.c |
FMM |
200 kA |
40 kA at 450V d.c. |
200 kA |
- |
MT |
200 kA |
40 kA at 350V d.c |
200 kA |
- |
MMT |
200 kA |
200 kA |
- |
Agency information
-
CE
-
Designed and tested to BS88 part 4
-
IEC 60269 Part 4
-
Consult fusetech@eaton.com for specific UL recognition status
-
CCC for ET, FE, EET, FEE, FM and FMM
Features and benefits
-
Excellent cycling capability and DC performance
-
Low arc voltage and low energy let-through (I2t)
-
Low watts loss
Typical applications
-
DC common bus
-
DC drives
-
Power converters/rectifiers
-
Reduced voltage starters
Carton quantity
-
LCT and CT: 20 per carton
-
LET, ET and FE: 10 per carton
-
EET, FEE: 5 per carton
-
LMT, LMMT, FM, FMM, MT and MMT: 1 per carton
Carton weight
-
LCT: 0.11kg
-
LET: 0.31kg
-
LMT: 0.18kg
-
LMMT: 0.37kg
-
CT: 0.16kg
-
ET and FE: 0.42kg
-
EET, FEE and FMM: 0.45kg
-
FM: 0.24kg
-
MT: 0.26kg
-
MMT: 0.47kg
Technical data - CT, ET, FE, EET, FEE
Catalogue numbers |
Rated voltage V a.c. / V d.c. |
Rated current RMSAmps |
Pre-arc |
I 2t (A2 Sec) |
Watts loss** |
|
Clearing at 415V |
Clearing at 660V |
|||||
6CT |
690 Vac / 500 Vdc (IEC) 700 Vac / 500 Vdc (UL) |
6 |
1.8 |
8.5 |
12 |
2 |
10CT |
10 |
7 |
30 |
48 |
3 |
|
12CT |
12 |
10 |
40 |
65 |
3 |
|
16CT |
16 |
16 |
66 |
110 |
7 |
|
20CT |
20 |
32 |
150 |
220 |
7 |
|
25ET |
690 Vac/ 500 Vdc (IEC) 700 Vac/ 500 Vdc (UL) |
25 |
25 |
150 |
250 |
7 |
32ET |
32 |
32 |
190 |
350 |
11 |
|
35ET |
35 |
52 |
310 |
500 |
11 |
|
40ET |
40 |
103 |
600 |
900 |
9 |
|
45ET |
45 |
103 |
680 |
110 |
11 |
|
56ET |
56 |
135 |
950 |
1500 |
14 |
|
63ET |
63 |
171 |
1200 |
2000 |
16 |
|
80ET |
80 |
360 |
2500 |
4000 |
18 |
|
35FE |
690 Vac / 500 Vdc (IEC) 700 Vac / 500 Vdc (UL) |
35 |
33 |
130 |
200 |
9 |
40FE |
40 |
52 |
180 |
300 |
9 |
|
45FE |
45 |
76 |
270 |
450 |
11 |
|
50FE |
50 |
103 |
380 |
600 |
11 |
|
63FE |
63 |
135 |
480 |
750 |
18.5 |
|
71FE |
71 |
210 |
600 |
950 |
17 |
|
80FE |
80 |
250 |
900 |
1500 |
20 |
|
90FE |
90 |
360 |
1300 |
2100 |
20 |
|
100FE |
100 |
470 |
180 |
2800 |
23 |
|
90EET |
690 Vac/ 500 Vdc (IEC) 700 Vac/500 Vdc (UL) |
90 |
490 |
3000 |
4500 |
19 |
110EET |
110 |
600 |
4000 |
6500 |
27 |
|
140EET |
140 |
1050 |
7000 |
12000 |
35 |
|
160EET |
160 |
1500 |
10000 |
17000 |
39 |
|
100FEE |
690 Vac / 500 Vdc (IEC) 700 Vac / 500 Vdc (UL) |
100 |
400 |
1600 |
2400 |
24 |
120FEE |
120 |
540 |
1900 |
3100 |
32 |
|
140FEE |
140 |
850 |
2500 |
3800 |
36 |
|
160FEE |
160 |
100 |
3700 |
5700 |
46 |
|
180FEE |
180 |
1400 |
5300 |
8400 |
46 |
|
200FEE |
200 |
1900 |
7100 |
11400 |
52 |
**Watts loss provided at rated current
Technical data - FM, FMM, MT and MMT
Catalogue numbers |
Rated voltage V a.c. / V d.c. |
Rated current RMSAmps |
Pre-arc |
I 2t (A2 Sec) |
Watts loss** |
|
Clearing at 415V |
Clearing at 660V |
|||||
180FM |
690 Vac / 450 Vdc (IEC) 700 Vac / 500 Vdc (UL) |
180 |
1400 |
7500 |
13500 |
40 |
200FM |
200 |
2600 |
10500 |
18500 |
40 |
|
225FM |
225 |
3700 |
14500 |
26500 |
44 |
|
250FM |
250 |
5200 |
20500 |
37500 |
48 |
|
280FM |
280 |
7000 |
30500 |
55000 |
48 |
|
315FM |
315 |
10000 |
40000 |
77000 |
55 |
|
350FM |
350 |
15000 |
60000 |
105000 |
55 |
|
400FMM |
690 Vac / 450 Vdc (IEC) 700 Vac (UL) |
400 |
10000 |
40000 |
72500 |
85 |
450FMM |
450 |
15000 |
60000 |
105000 |
90 |
|
500FMM |
500 |
20000 |
82000 |
150000 |
100 |
|
550FMM |
550 |
30000 |
120000 |
215000 |
100 |
|
630FMM |
630 |
45000 |
180000 |
310000 |
100 |
|
700FMM |
700 |
60000 |
245000 |
420000 |
120 |
|
160MT |
690 Vac / 350 Vdc (IEC) 700 Vac (UL) |
160 |
2400 |
15000 |
25000 |
26 |
180MT |
180 |
3800 |
25000 |
38000 |
26 |
|
200MT |
200 |
600 |
40000 |
58000 |
27 |
|
250MT |
250 |
11500 |
80000 |
110000 |
32 |
|
280MT |
280 |
16500 |
100000 |
150000 |
35 |
|
315MT |
315 |
19000 |
125000 |
180000 |
42 |
|
355MT |
355 |
22000 |
160000 |
200000 |
51 |
|
180MMT |
690 Vac / 350 Vdc (IEC) 700 Vac (UL) |
180 |
1650 |
12000 |
18000 |
42 |
200MMT |
200 |
2200 |
16000 |
23000 |
42 |
|
225MMT |
225 |
37000 |
26000 |
40000 |
42 |
|
280MMT |
280 |
6600 |
47000 |
70000 |
47 |
|
315MMT |
315 |
8600 |
62000 |
91000 |
51 |
|
355MMT |
355 |
13500 |
97000 |
140000 |
54 |
|
400MMT |
400 |
21000 |
150000 |
220000 |
60 |
|
450MMT |
450 |
30000 |
220000 |
320000 |
57 |
|
500MMT |
500 |
42000 |
300000 |
450000 |
64 |
|
560MMT |
560 |
60000 |
430000 |
640000 |
64 |
|
630MMT |
630 |
88500 |
500000 |
720000 |
86 |
|
710MMT |
710 |
78000 |
600000 |
850000 |
105 |
Series: EET series, BS 88 standard double tube fast fuse
Current: 90-160A
Voltage: 690Vac/500Vdc
Breaking capacity: 200kA RMS Sym.
Certifications: CE, Designed and tested to: BS 88 Part 4, IEC 269 Part 4, UL Recognized. Consult Cooper Bussmann or Bolfmax for UL Recognition status.