Fusetron™ 600V Class RK5 FRS-R - 600 Vac/300 Vdc, 1/10-60 A, dual element, time-delay fuses
Catalog symbol:
-
FRS-R-(amp) (non-indicating)
-
FRS-R-(amp)ID (indicating)
Description:
Advanced protection, energy efficient Class RK5 dual-element, current-limiting, time-delay fuses with optional open fuse indication on select ratings. Time-delay - 10 second (minimum) at 500% of rated current.
Specifications:
Ratings
Volts:
-
600 Vac, 300 Vdc (1/10-30 A)
-
600 Vac, 250 Vdc* (35-60 A)
Amps:1/10 -600A
Interrupting rating
-
200 kA Vac RMS Sym
-
20 kA Vdc
Agency information
-
UL® Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
-
CSA® Certified, C22.2 No. 248.12, Class 1422-02, File 53787
-
CE
Catalog Numbers (Amps)
FRS-R-1/10 |
FRS-R-1-1/4 |
FRS-R-4 |
FRS-R-15 |
FRS-R-1/8 |
FRS-R-1-4/10 |
FRS-R-4-1/2 |
FRS-R-17-1/2 |
FRS-R-15/100 |
FRS-R-1-1/2 |
FRS-R-5 |
FRS-R-20 |
FRS-R-2/10 |
FRS-R-1-6/10 |
FRS-R-5-6/10 |
FRS-R-25 |
FRS-R-1/4 |
FRS-R-1-8/10 |
FRS-R-6 |
FRS-R-30 |
FRS-R-3/10 |
FRS-R-2 |
FRS-R-6-1/4 |
FRS-R-35 |
FRS-R-4/10 |
FRS-R-2-1/4 |
FRS-R-7 |
FRS-R-40 |
FRS-R-1/2 |
FRS-R-2-1/2 |
FRS-R-7-1/2 |
FRS-R-45 |
FRS-R-6/10 |
FRS-R-2-8/10 |
FRS-R-8 |
FRS-R-50 |
FRS-R-8/10 |
FRS-R-3 |
FRS-R-9 |
FRS-R-60 |
FRS-R-1 |
FRS-R-3-2/10 |
FRS-R-10 |
|
FRS-R-1-1/8 |
FRS-R-3-1/2 |
FRS-R-12 |
|
* Open fuse indication available by inserting the suffix “ID." E.g., FRS-R-15ID. 35 to 60 amp indicating fuses are not Vdc rated.
Carton Quantity
Amp Rating |
Carton Qty. |
1-60 |
10 |
Features and benefits
-
Dual-element feature provides the best time-delay performance, allowing closer sizing and superior protection of motors and transformers
-
Closer sizing allows for smaller fuses and less costly switches
-
Class RK5 fuses with a 200 kA interrupting rating for use in a broad range of applications
-
Provides motor overload, ground fault, and short-circuit protection
-
Helps protect motors against burnout from overloads and single-phasing when sized properly
-
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance
short-circuit and overload protection
-
Offers a 10-second time delay at 5 times the rated current
-
The time-delay feature makes it possible to use fuse amp ratings that are much smaller than those of non-time delay fuses. Considerable
cost savings occur by permitting the use of smaller size switches, panels, and fuses themselves.
-
Provides current limitation to help protect downstream components from high fault currents.
-
Gives motor running back-up protection to motors without extra costs.
Recommended fuse blocks
Amps |
Catalog no |
||
1-Pole |
2-Pole |
3-Pole |
|
30 |
RM60030-1_ |
RM60030-2_ |
RM60030-3_ |
60 |
RM60060-1_ |
RM60060-2_ |
RM60060-3_ |
For additional information on the 600 volt fuse blocks, see data sheet no. 10489. For additional information on the RM600 volt fuse blocks, see data sheet No. 10489
Fuse reducers for Class R fuses
Equipment fuse clips |
Desired fuse (case) |
Catalog no. (pairs) |
size |
600V |
|
60A |
30A |
NO.663-R |
100A |
30A |
NO.246-R |
60A |
NO.616-R |
|
200A |
60A |
NO.626-R |
Current-limiting effects
Prosp. S.C.C. |
Let-through current |
|
(apparent RMS symmetrical vs. fuse rating) |
||
- |
30A |
60A |
5000 |
1000 |
1000 |
10000 |
1000 |
2000 |
15000 |
1000 |
2000 |
20000 |
2000 |
2000 |
25000 |
2000 |
2000 |
30000 |
2000 |
3000 |
35000 |
2000 |
3000 |
40000 |
2000 |
3000 |
50000 |
2000 |
3000 |
60000 |
2000 |
3000 |
70000 |
3000 |
4000 |
80000 |
3000 |
4000 |
90000 |
3000 |
4000 |
100000 |
3000 |
4000 |
150000 |
3000 |
5000 |
200000 |
4000 |
6000 |
Fusetron™ 600V Class RK5 FRS-R - 600 Vac/300 Vdc, 65-600 A, dual element, time-delay fuses
Catalog symbol:FRS-R-(amp)
Description:
Advanced protection, energy efficient Class RK5 dual element, current-limiting, time-delay fuses. Time-delay - 10 seconds (minimum) at 500% of rated current.
Specifications:
Ratings
Volts:600Vac, 300Vdc
Amps:65-600A
Interrupting rating
-
200 kA Vac RMS Sym
-
20 kA Vdc
Agency information:
-
UL® Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273
-
CSA® Certified, C22.2 No. 248.12, Class 1422-02, File 53787
-
CE
Catalog numbers (amps):
FRS-R-65 |
FRS-R-100 |
FRS-R-200 |
FRS-R-400 |
FRS-R-70 |
FRS-R-110 |
FRS-R-225 |
FRS-R-450 |
FRS-R-75 |
FRS-R-125 |
FRS-R-250 |
FRS-R-500 |
FRS-R-80 |
FRS-R-150 |
FRS-R-300 |
FRS-R-600 |
FRS-R-90 |
FRS-R-175 |
FRS-R-350 |
|
Carton quantity:
Amp Rating |
Carton Qty. |
65-100 |
1 |
101-200 |
1 |
201-400 |
1 |
401-600 |
1 |
Features:
-
Provides motor overload, ground fault and short-circuit protection. When used in circuits subject to surge currents such as those caused
by motors, transformers and other inductive components, these fuses can be sized close to full-load amps to give maximum overcurrent
protection
-
The time-delay feature makes it possible to use fuse amp ratings which are much smaller than those of non-time delay fuses. Considerable
cost saving occurs by permitting the use of smaller size switches, panels and fuses themselves
-
Provides a good degree of short-circuit protection (greater current-limitation) to help protect downstream components from high fault currents
-
Gives motor running back-up protection to motors without extra cost
-
Helps protect motors against burnout from overloads and single-phasing when sized properly
-
Simplifies and improves blackout prevention (selective coordination ratios)
-
Dual-element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high-performance,
short-circuit and overload protection
Dimensions - in:
Amp ratings |
A |
B |
65-100 |
7.88 |
1.11 |
1110-200 |
9.63 |
1.61 |
225-400 |
11.63 |
2.34 |
450-600 |
13.38 |
2.88 |
Recommended fuse blocks:
Fuse amps |
1-Pole |
2-Pole |
3-Pole |
70-100 |
RM60100-1CR |
RM60100-2CR |
RM60100-3CR |
110-200 |
RM60200-1CR |
RM60200-2CR |
RM60200-3CR |
225-400 |
RM60400-1CR |
RM60400-2CR |
RM60400-3CR |
450-600 |
RM60600-1CR |
RM60600-2CR |
RM60100-3CR |
Fuse reducers for class R fuses:
Equipment fuse clips |
Desired fuse (case) size |
Catalog numbers (pairs) 600V |
200A |
100A |
NO.2621-R |
400A |
100A |
NO.2641-R |
200A |
NO.642-R |
|
100A |
NO.2661-R |
|
600A |
200A |
NO.2662-R |
400A |
NO.2664-R |
†Single reducer only (pair not required).
For additional information on Class R fuse reducers, see data sheet No. 1118.
Current-limiting effects:
Prospective S.C.C. |
Let-through current |
|||
(apparent RMS symmetrical vs. fuse rating) |
||||
|
100A |
200A |
400A |
600A |
5000 |
3000 |
4000 |
5000 |
5000 |
10000 |
4000 |
5000 |
9000 |
10000 |
15000 |
4000 |
60000 |
10000 |
14000 |
20000 |
5000 |
7000 |
11000 |
15000 |
25000 |
5000 |
7000 |
12000 |
17000 |
30000 |
5000 |
8000 |
13000 |
18000 |
35000 |
5000 |
8000 |
13000 |
18000 |
40000 |
6000 |
9000 |
14000 |
19000 |
50000 |
6000 |
9000 |
14000 |
20000 |
60000 |
6000 |
10000 |
15000 |
22000 |
70000 |
7000 |
11000 |
17000 |
23000 |
80000 |
7000 |
12000 |
17000 |
23000 |
90000 |
7000 |
12000 |
17000 |
24000 |
100000 |
8000 |
13000 |
18000 |
25000 |
150000 |
9000 |
14000 |
21000 |
27000 |
200000 |
9000 |
16000 |
23000 |
32000 |
Series : FRS-R series, double indication delay slow RK5 fuse
Current : 1/10 -600A
Voltage :
600 Vac, 300 Vdc (1/10-30 A)
600 Vac, 250 Vdc (35-60 A)
600 Vac, 300 Vdc (65-600 A)
Breaking capacity: 200 kA Vac RMS Sym.20 kA Vdc
Certifications: UL® Listed, Std. 248-12, Class RK5, Guide JDDZ, File E4273.CSA® Certified, C22.2 No. 248.12, Class 1422-02, File 53787.CE.